Solenoid valve non-action failure and troubleshooting method

The failure of the solenoid valve will directly affect the action of the switching valve and the regulating valve. The common faults are that the solenoid valve does not operate. The following aspects should be checked:

(1) The solenoid valve terminal is loose or the wire ends are off, the solenoid valve is not energized, and the wire end can be tightened.

(2) When the solenoid valve coil is burnt out, the wiring of the solenoid valve can be removed and measured with a multimeter. If the circuit is open, the solenoid valve coil is burned out.

The reason is that the coil is damp, causing poor insulation and magnetic leakage, causing the current in the coil to be too large and burning, so it is necessary to prevent rainwater from entering the solenoid valve. In addition, the spring is too hard, the reaction force is too large, the number of turns of the coil is too small, and the suction force is insufficient to cause the coil to burn. For emergency handling, the manual button on the coil can be turned from the “0” position to the “1” position during normal operation, causing the valve to open.

(3) The solenoid valve is stuck. The clearance between the sliding valve sleeve of the solenoid valve and the valve core is very small (less than 0.008 mm), and it is generally a one-piece assembly. When mechanical impurities are introduced or the lubricating oil is too small, it is easy to get stuck. The treatment method can use the steel wire to break in from the small hole of the head to make it bounce back. The fundamental solution is to remove the solenoid valve, take out the valve core and the valve core sleeve, and clean it with CCI4, so that the valve core can move flexibly in the valve sleeve. When disassembling, pay attention to the assembly sequence and external wiring position of each component, so as to reassemble and wire correctly, and check whether the oil mist injection hole is blocked and the lubricating oil is sufficient.

(4) Air leakage. Leakage can cause insufficient air pressure, making it difficult to open and close the forced valve due to damage to the gasket or wear of the spool to cause several cavity helium.

When dealing with the solenoid valve failure of the switching system, the appropriate timing should be selected, and the solenoid valve should be processed when the power is lost. If the processing is not completed within one switching gap, the switching system can be suspended and taken care of.

Sauna Shower Combination

The Sauna Shower Room is a luxurious and innovative addition to any bathroom or wellness space. Combining the relaxation benefits of a sauna with the convenience of a shower, this versatile unit offers a unique and rejuvenating experience.

In addition to its sauna capabilities, the shower function of the room is equally impressive. The showerhead is designed with multiple settings, ensuring a refreshing and invigorating shower experience.

The Sauna Shower Room is not only a luxurious addition to any home, but it also offers numerous health benefits. Saunas are known to promote relaxation, improve blood circulation, detoxify the body, and relieve muscle tension. The combination of sauna and shower functions in one unit makes it a convenient and space-saving option for those seeking a comprehensive wellness experience.

steam shower room,steam shower cabin,sauna and shower room,Combi Sauna room

Foshan Nanhai Halo Sanitary Ware Co., Ltd. , https://www.halospas.com